产品简介:
Detcon Model 12 single channeldigital control modules are designedto supervise and display the status of a single remote sensor assembly.Modules are available for a variety of toxic and combusti

详细介绍

北京松信宏泽科技有限公司

:潘女士

Model 12B 单卡报警控制器

产品简介:
Detcon Model 12 single channeldigital control modules are designedto supervise and display the status of a single remote sensor assembly.Modules are available for a variety of toxic and combustible gases and are compatible with a complete line of Detcon enclosures and mainframe hardware assemblies.

Model 12B 单卡报警控制器

技术参数:
Range
     0-100 ppm/% standard
     Other ranges available
Accuracy/Repeatability
± 2% F.S.
Operating Temperature Range
     -40°C to +80°C; -40°F to +175°F
Input Voltage
     24 VDC standard
Power Consumption
     <3 watts: <5 watts (full alarm)
Outputs
     Analog 4-20 mA DC
     Serial RS-485 Modbus™
Relays
     Alarm 1, Alarm 2, Alarm 3, Fault
     Jumper Selectable Form "A" or Form "B"
     Contacts rated 5 amps @ 30 VDC

 Modular plug-in design
4 to 12 channel packaging: NEMA 1, 4X, and 7
Compatible with PLC’s, SCADA, DCS
Outputs: 4-20 mA, RS-485, and 3 alarm relays
Status and parameters accessible via RS-485
 Programmable relays standard (3 alarms + fault)
Five year fixed-fee service policy
Alarm disable function

Three digit indicator serves as both a power on indicator and
a direct reading display of the gas concentration. The display
will also flash on and off during any over-range condition.

Alarm set points are dip switch adjustable in 1 ppm/%
increments across the range of detection. Programmable jumpers
allow for several user selectable alarm options.

The fault alarm, depending on the jumper programmable
configuration, will activate on loss of power, internal power
supply fault, open circuit in field wiring, open heater/bridge
in sensor, or during an alarm disable condition.

The alarm disable function inhibits alarm relays (Alarm 1, 2
and 3), but leaves alarm LEDs active. The alarm disable
function will also activate the fault LED and relay, however,
no other Model 12 functions are af fected. The toggle type
switch is inset slightly behind the front panel in order to
prevent accidental disabling of the channel.

The alarm reset switch resets alarms that have been jumper
programmed latching. It also acts as a test switch to activate
several microprocessor supervised test functions.