安装使用多极管式滑触线的注意事项:
Installation using multipole tube slide wire notice:
1、潮湿状态或室外使用,请用绝缘子的悬吊螺栓。
1, moist state or outdoor use, please use the suspension insulator bolt.
2、全线安装后,测量外壳与带电体间绝缘电阻不得小于5MW,测量外壳的电连续性,将一端导轨与外壳搭接,然后另一端测量回路是否畅通,测定完毕后,拆除连接部分。多级管式滑触线
2, all after installation, measure the insulation resistance between the shell and the charged body shall not be less than 5 mw, measuring casing electrical continuity, guide rail and the shell will end lap, and then the other end of the measurement circuit is open, after the determination, remove the connection parts.
3、为防止集电器颈部磨损,对集电器颈部外包不锈钢护壳、或保护滚柱应定期检查,及时更换。
3, in order to prevent the collector neck wear and tear, the collector neck outsourcing stainless steel shell, or protect roller should be checked regularly, timely replacement.
4、室外雨雪、湿度较大场所,导管外壳连接处,绝缘粘带缠覆后再盖连接夹,以防止雨水侵入。
4, outdoor snow and rain, humidity larger place, catheter shell joints, insulation adhesive tape wrapped cover again after connecting clip, in order to prevent water invasion.
5、铝合金型外壳必须良好的接地,全线外壳保证电连续性,外壳每隔25m-30m接地一次。
5, aluminum alloy shell must be good grounding, across the shell to ensure electrical continuity, shell every 25 m to 30 m ground again.