、KVVP用途:本产品供交流额定电压500V或直流电压1000V及以下配电装置中电器,仪表接线之用。
2、KVVP产品使用特性:电缆导体的长期允许工作温度应不超过70℃。敷设时电缆的温度应不低于0℃,敷设时弯曲半径应不小于电缆外径的10倍。有铠装层或铜带屏蔽结构的电缆,应不小于电缆外径的12倍。
3、KVVP产品标准:GB9330.2-88《聚氯乙烯绝缘和护套控制电缆》额定电压:450/750V
芯数×标称截 面mm2 | 导体种类 | 绝 缘厚 度mm | KVVP型屏蔽密度% | 护套厚度mm | 平均外径尺寸mm | 70度时绝缘电阻zui小值MΩ·km |
KVV型 | KVVP型 |
2×0.75 | 1 | 0.6 | | 1.2 | 7.74 | | 0.012 |
2×0.75 | 2 | 0.6 | 65~80 | 1.2 | 8.02 | 8.62 | 0.014 |
2×1.0 | 1 | 0.6 | | 1.2 | 8.06 | | 0.011 |
2×1.0 | 2 | 0.6 | 65~80 | 1.2 | 8.38 | 8.98 | 0.013 |
2×1.5 | 1 | 0.7 | | 1.2 | 8.96 | | 0.011 |
2×1.5 | 2 | 0.7 | 65~80 | 1.2 | 9.32 | 9.92 | 0.012 |
2×2.5 | 1 | 0.8 | | 1.2 | 10.16 | | 0.010 |
2×2.5 | 2 | 0.8 | 65~80 | 1.2 | 10.68 | 11.28 | 0.009 |
2×4 | 1 | 0.8 | | 1.2 | 11.1 | | 0.0077 |
2×4 | 2 | 0.8 | 65~80 | 1.2 | 11.7 | 13.1 | 0.0085 |
2×6 | 1 | 0.8 | | 1.5 | 12.12 | | 0.0070 |
2×6 | 2 | 0.8 | 65~80 | 1.5 | 12.84 | 14.24 | 0.0065 |
2×10 | 2 | 1.0 | 65~80 | 1.5 | 15.5 | 16.9 | 0.0065 |
3×0.75 | 1 | 0.6 | | 1.2 | 8.07 | | 0.012 |
3×0.75 | 2 | 0.6 | 65~80 | 1.2 | 8.38 | 8.98 | 0.014 |
3×1.0 | 1 | 0.6 | | 1.2 | 8.42 | | 0.011 |